Item |
Specifications |
Model |
FP3500-T41-24V |
Electrical |
Rated Voltage
(Rated Frequency) |
DC24V |
Power Consumption |
2.08A or less
(TYP 1.08A) |
Allowable Voltage Drop |
Within 10ms |
Voltage Endurance |
AC1000V 20mA for 1 minute |
Insulation Resistance |
10MΩ or more at DC500V
(between charging and FG terminals)
|
Environmental |
Ambient Operating Temperature*3 |
0°C to 50°C
(within 30° from the installing angle vertical direction) |
Ambient Humidity |
10%RH to 90%RH
(no condensation)(wet-bulb temperature: 39°C or lower) |
Storage Temperature |
-20 °C to +60 °C |
Storage Humidity |
10%RH to 90%RH
(no condensation)(wet-bulb temperature: 39°C or lower) |
Corrosive Gases |
Free of corrosive gases |
Noise Immunity
(via noise simulator) |
Noise Voltage: 1000Vp-p
Pulse Duration: 1μs Rise Time: 1ns |
Grounding |
Protective and Functional Grounding: D-type grounding |
Electrostatic Discharge Immunity |
6kV (EN61000-4-2 Level 3)
|
Vibration Resistance |
JIS B 3502, IEC61131-2 compatible
5Hz to 9Hz Half Amplitude 3.5mm
9Hz to 150Hz Constant Acceleration 9.8m/s2
Applied in X, Y and Z directions 10 cycles for 100 minutes
|
Structural |
Rating |
Equivalent to IP65f (only for the front area when the panel is installed)*4 |
Weight |
Approx. 3.5kg [7.7lb] |
External Dimensions
(W × H × D) |
317mm [12.48in.] × 243mm [9.57in.] × 58mm [2.28in.] |