详细介绍: ES710/5KVA,ES710/5000,ES710-5KVA,ES710-5000
ES710/3150/4000/5000/6300/8000/10000提供ES710-3.15KVA隔离变压器、ES710-4KVA隔离变压器、ES710-5KVA隔离变压器、ES710-6.3KVA隔离变压器、ES710-8KVA隔离变压器、ES710-10KVA隔离变压器、ES710/3150隔离变压器、ES710/4000隔离变压器、ES710/5000隔离变压器、ES710/6300隔离变压器、ES710/8000隔离变压器、ES710/10000隔离变压器 ES710医用隔离变压器ES710/3150,ES710-3150,ES710-3.15,ES710-3KVA,ES710-4000,ES710/4000,ES710-4KVA,ES710/4KVA,ES710-5000,ES710/5000,ES710-5KVA,ES710/5KVA,ES710-6KVA,ES710-6000,ES710/6000,ES710-7KVA,ES710/6.3KVA,ES710-6300,ES710/6300,ES710-7KVA,ES710/7KVA,ES710-8KVA,ES710/8000,ES710/8KVA,ES710/10000,ES710-10KVA,ES710/10KVA,ES710/8KVA,ES710/8000,ES710-8KVA,ES710/6300,ES710-6.3KVA,,ES710/6.3KVA,ES710-6300,ES710/3150,ES710-3150,ES710-3.15,ES710-3KVA,ES710-4000,ES710/4000,ES710-4KVA,ES710/4KVA,ES710-5000,ES710/5000,ES710-5KVA,ES710/5KVA,ES710/8KVA,ES710/8000,ES710-8KVA,ES710/6300,ES710-6.3KVA,ES710/6.3KVA,ES710-6300,ES710/3150,ES710-3150,ES710-3.15,ES710-3KVA,ES710-4000ES710/4000,ES710-4KVA,ES710/4KVA,ES710-5000ES710/5000,ES710-5KVA,ES710/5KVAES710-3.15KVA隔离变压器、ES710-4KVA隔离变压器、ES710-5KVA隔离变压器、ES710-6.3KVA隔离变压器、ES710-8KVA隔离变压器、ES710-10KVA隔离变压器、ES710/3150隔离变压器、ES710/4000隔离变压器、ES710/5000隔离变压器、ES710/6300隔离变压器、ES710/8000隔离变压器、ES710/10000隔离变压器为医疗建筑物2类场所医用变压器.
手术室,重症监护室ICU CCU等特殊场合使用的医用隔离电源系统须含有以下系统
1每间I级手术间按原设计配电思路以及总负荷配备不应小于10KVA,且必须设置≥6.3KVA隔离变压器构成的IT系统(包括隔离变压器、绝缘监测仪、电流互感器、仪器专用电源、外接报警显示和测试单元); 每间Ⅲ级手术室总配电负荷不应小于8KVA,IT系统≥6.3KVA隔离变压器构成的;IT系统最大分断时间230V应为0.2S.
2医用隔离电源系统由医用隔离变压器,绝缘监测,外接报警装置,断路器等主要元件组成,并符合以下标准:
3 满足《建筑物电气装置第7-710部分:特殊装置或场所得要求—医疗场所》GB16895.24-2005 / IEC60364-7-710:2002 710.512.1.6中规定:医用隔离变压器应符合IEC61558-2-15的要求。
4 变压器的二次侧额定电压Un不应超过250V,用于移动式和固定式设备的医疗IT系统应采用单相变压器,其额定输出容量不应小于0.5KVA,但不应超过10KVA。
5 医用隔离变压器的金属外壳需与局部等电位联结端子板联结。
6绝缘监测仪
7绝缘监视报警系统符合IEC61557-8和IEC60364-7-710标准。
8交流内阻抗应至少为100kΩ;测试电压不应大于直流25V;即使在故障情况下,其注入电流的峰值不应大于1Ma;最迟在绝缘电阻降至50 kΩ时,应发出信号。应配置试验此功能的器具。
9报警显示系统
医用隔离电源 医用隔离变压器医用绝缘监视仪 漏电监测仪(剩余电流监视仪)漏电监视仪系统(剩余电流监视仪系统)