Article No.
|
6ES7 307-1BA01-0AA0
|
Technical specifications
|
|
Product
|
PS 307
|
Power supply, type
|
24 V/2 A
|
Input
|
|
Input
|
1-phase AC
|
Supply voltage
|
|
|
120V
|
|
230V
|
|
|
|
Automatic range selection
|
Input voltage
|
|
|
85…132V
|
|
170…264V
|
|
|
Overvoltage resistance
|
2.3 × Vin rated, 1.3 ms
|
Mains buffering at Iout rated, min.
|
0.02s
|
Mains buffering
|
at Vin = 93/187 V
|
Rated line frequency
|
|
|
50Hz
|
|
60Hz
|
Rated line range
|
47…63Hz
|
Input current
|
|
-
at nominal level of the input voltage 120 V nominal value
|
0.9A
|
-
at nominal level of the input voltage 230 V nominal value
|
0.5A
|
-
at nominal level of the input voltage 24 V nominal value
|
|
-
at nominal level of the input voltage 110 V nominal value
|
|
Switch-on current limiting (+25 °C), max.
|
22A
|
Duration of current limiting at 25 °C maximum
|
3ms
|
I²t, max.
|
1A²·s
|
Built-in incoming fuse
|
T 1.6 A/250 V (not accessible)
|
Protection in the mains power input (IEC 898)
|
Recommended miniature circuit breaker: 3 A characteristic C
|
Output
|
|
Output
|
Controlled, isolated DC voltage
|
Rated voltage Vout DC
|
24V
|
Total tolerance, static ±
|
3%
|
Static mains compensation, approx.
|
0.1%
|
Static load balancing, approx.
|
0.2%
|
Residual ripple peak-peak, max.
|
50mV
|
Residual ripple peak-peak, typ.
|
5mV
|
Spikes peak-peak, max. (bandwidth: 20 MHz)
|
150mV
|
Spikes peak-peak, typ. (bandwidth: 20 MHz)
|
20mV
|
Product feature output voltage adjustable
|
No
|
Output voltage setting
|
-
|
Status display
|
Green LED for 24 V OK
|
On/off behavior
|
No overshoot of Vout (soft start)
|
Startup delay, max.
|
2s
|
Voltage rise, typ.
|
10ms
|
Rated current value Iout rated
|
2A
|
Current range
|
0…2A
|
Note
|
|
delivered active power typ.
|
48W
|
short-term overload current at short-circuit during run-up typical
|
9A
|
Duration of overloading ability for excess current on short-circuiting during the start-up
|
90ms
|
short-term overload current at short-circuit during operation typical
|
9A
|
Duration of overloading ability for excess current on short-circuiting during the operational phase
|
90ms
|
Parallel switching for enhanced performance
|
Yes
|
Numbers of parallel switchable units for enhanced performance
|
|
Efficiency
|
|
Efficiency at Vout rated, Iout rated, approx.
|
84%
|
Power loss at Vout rated, Iout rated, approx.
|
9W
|
Closed-loop control
|
|
Dynamic mains compensation (Vin rated ±15 %), max.
|
0.1%
|
Dynamic load smoothing (Iout: 50/100/50 %), Uout ± typ.
|
0.8%
|
Load step setting time 50 to 100%, typ.
|
0.5ms
|
Load step setting time 100 to 50%, typ.
|
0.5ms
|
Setting time maximum
|
1ms
|
Protection and monitoring
|
|
Output overvoltage protection
|
Additional control loop, shutdown at < 28.8 V, automatic restart
|
Current limitation
|
2.2…2.6A
|
Characteristic feature of the output short-circuit protected
|
Yes
|
Short-circuit protection
|
Electronic shutdown, automatic restart
|
Enduring short circuit current Effective level maximum
|
2A
|
Overload/short-circuit indicator
|
-
|
Safety
|
|
Primary/secondary isolation
|
Yes
|
Potential separation
|
Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178
|
Protection class
|
Class I
|
stray current
|
|
|
3.5mA
|
|
0.5mA
|
CE mark
|
Yes
|
UL/CSA approval
|
Yes
|
UL/cUL (CSA) approval
|
cULus-Listed (UL 508, CSA C22.2 No. 142), File E143289
|
Explosion protection
|
ATEX (EX) II 3G Ex nA II T4; cULus (ISA 12.12.01, CSA C22.2 No.213) Class I, Div. 2, Group ABCD, T4, File E330455
|
FM approval
|
YesClass I, Div. 2, Group ABCD, T4
|
CB approval
|
No
|
Marine approval
|
In S7-300 system
|
Degree of protection (EN 60529)
|
IP20
|
EMC
|
|
Emitted interference
|
EN 55022 Class B
|
Supply harmonics limitation
|
not applicable
|
Noise immunity
|
EN 61000-6-2
|
Operating data
|
|
Ambient temperature
|
|
|
0…60°C
|
|
with natural convection
|
Ambient temperature
|
|
|
-40…+85°C
|
Ambient temperature
|
|
|
-40…+85°C
|
Humidity class according to EN 60721
|
Climate class 3K3, no condensation
|
Mechanics
|
|
Connection technology
|
screw-type terminals
|
Connections
|
|
|
L, N, PE: 1 screw terminal each for 0.5 ... 2.5 mm² single-core/finely stranded
|
|
L+, M: 2 screw terminals each for 0.5 ... 2.5 mm²
|
|
-
|
Width of the housing
|
40mm
|
Height of the housing
|
125mm
|
Depth of the housing
|
120mm
|
Installation width
|
40mm
|
Installation height
|
205mm
|
Weight, approx.
|
0.4kg
|
Product feature of the housing housing for side-by-side mounting
|
Yes
|
Mounting type
|
|
|
No
|
|
No
|
|
Yes
|
Installation
|
Can be mounted onto S7 rail
|
Mechanical accessories
|
Mounting adapter for standard mounting rail (6EP1971-1BA00)
|