General specifications |
Switching element function |
NAMUR, NC |
Rated operating distance |
4 mm |
Installation |
non-flush |
Output polarity |
NAMUR |
Assured operating distance |
0 ... 3.24 mm |
Reduction factor rAl |
0.4 |
Reduction factor rCu |
0.3 |
Reduction factor r304 |
0.85 |
Nominal ratings |
Nominal voltage |
8.2 V (Ri approx. 1 kΩ) |
Operating voltage |
5 ... 25 V |
Switching frequency |
0 ... 1500 Hz |
Hysteresis |
3 % |
Current consumption |
|
|
Measuring plate not detected |
min. 3 mA |
|
Measuring plate detected |
≤ 1 mA |
Compliance with standards and directives |
Standard conformity |
|
|
NAMUR |
EN 60947-5-6:2000
IEC 60947-5-6:1999 |
Approvals and certificates |
FM approval |
|
|
Control drawing |
116-0165F |
UL approval |
cULus Listed, General Purpose |
CSA approval |
cCSAus Listed, General Purpose |
CCC approval |
CCC approval / marking not required for products rated ≤36 V |
Ambient conditions |
Ambient temperature |
-25 ... 100 °C (-13 ... 212 °F) |
Mechanical specifications |
Connection type |
Connector M12 x 1 , 4-pin |
Housing material |
Stainless steel 1.4305 / AISI 303 |
Sensing face |
PBT |
Housing diameter |
12 mm |
Protection degree |
IP67 |
General information |
Scope of delivery |
2 self locking nuts in scope of delivery |
Use in the hazardous area |
see instruction manuals |
|
Category |
1G; 2G |