原装进口CIRCUTOR(西谷铎)MYeBOX-1500便携式电能质量分析仪柔性互感器测量
原装进口CIRCUTOR(西谷铎)MYeBOX-1500便携式电能质量分析仪柔性互感器测量
产品价格:¥99999999999(人民币)
  • 规格:MYeBOX-1500
  • 发货地:巴塞罗那
  • 品牌:
  • 最小起订量:1套
  • 诚信商家
    会员级别:钻石会员
    认证类型:未认证
    企业证件:未通过
    认证信息:未认证

    商铺名称:CIRCUTOR(西谷铎) 驻大中华区办事处

    联系人:(小姐)

    联系手机:

    固定电话:

    企业邮箱:shanghai@circutor.com

    联系地址:南京西路1308号1606室

    邮编:200041

    联系我时,请说是在地方电气网上看到的,谢谢!

    商品详情

      项目询价 及 相关授权经销商查询,请联系:

      电话:021-52287226(直线)

      邮箱:shanghai@circutor.com

      中国大陆及港澳台地区,现由CIRCUTOR(西谷铎)大中华区办事处:

      CIRCUTOR(西谷铎)Shanghai上海

      统一负责管理



      MYeBOX-1500-4 FLEX-R80

      MYeBOX-1500-4 FLEX-R80, Portable power analyzer with recording of quality events and transients

      Code: M8405E0000A00

      • Nr Sensors: 4 FLEX-R80
      • Communications: Wi-Fi | 3G
      • Transistor output: 2
      • Digital inputs: 2
      • No. of voltage measurement inputs: 5
      • Measuring current Channels: 5
      • Class: Class A
      DESCRIPTION

      MYeBOX is a range of portable analyzers that can be configured from an app that analyses the accessible electrical parameters remotely. MYeBOX measures and records the electrical parameters in single, two or three-phase installations (with and without neutral).
      The app is connected to the device to display the data measured in real time, to fully configure the unit, to start or stop the data recording process, to send the recorded data to MYeBOX Cloud and even to access the data in the memory to display them in graphical form or in tables. Remote connectivity allows the unit to analyse all data measured without the need to travel to the site. Data recorded by the unit can also be sent to a data repository for its subsequent analysis in PowerVision Plus. The unit can be configured locally with a capacitive keypad and with the menu options shown on the screen.
      The most advanced model, MYeBOX 1500, can measure the leakage current simultaneously, it can measure the network quality parameters in compliance with the EN 50160 standard and also record the transients.
      MYeBOX 150 has the following features and functions:

      • 4 voltage measurement inputs (U1, U2, U3, Un)
      • 4 current measurement inputs (I1, I2, I3, In)
      • Measurement of the main electrical parameters
      • Energy consumed and generated
      • Measurement of network quality parameters
      • True RMS measurement (TRMS)
      • Measurement of consumption and generation (4Q)
      • Voltage quality event log, according to EN 61000-4-30
      • Transients log
      • Recording of the wave shape associated with the quality events and transients
      • Measurement according to EN 61000-4-30
      • Power supply is independent of the measurement
      • Recording of the wave shape for each recording period
      • LCD Screen
      • Capacitive keypad
      • Micro-USB port to download data
      • Automatic detection of clamps
      • Identification of phases with colours
      • Compatible with clamps with EEPROM
      • Recording of system events (EVA)
      • NTP synchronisation
      • Sending of alarms via e-mail
      • Wi-Fi communications (access point/terminal)

      In addition to these features and functions, MYeBOX 1500 also features:

      • 1 voltage measurement input Uref
      • 1 leakage current measurement input
      • 2 transistor inputs to centralise impulses / tariff / state
      • 2 transistor outputs for alarms
      • 3G communications
      APPLICATIONS

      MYeBOX can be used to:

      • Prepare complete studies of an electrical installation.
      • Analyse consumption, load curves, disturbances in the installation's voltage, display wave shapes, harmonics study or flicker measurement, among other options.
      • Perform audits and analyses remotely.
      AUXILIARY BATTERY POWER SUPPLY
      Autonomy
      2 h (without 3G), 50 min (with 3G)
      Battery type
      Litio (3,7 Vc.c.)
      Capacity
      3700 mAh
      Load temperature
      0 … 40 °C
      Load time
      6 h
      AC POWER SUPPLY
      Installation category
      CAT II 300 V
      Consumption
      22…28 VA
      Frequency
      47…63 Hz
      Nominal voltage
      100…240 Vc.a.(Adaptador de alimentación de c.a.)
      POWERED BY CHARGER, ADAPTER
      Output voltage
      9 Vc.c.
      Maximum power
      20 W
      SPECIFIC TECHNICAL CHARACTERISTICS OF CURRENT SENSORS
      Linearity
      2 % (10…200 % In)
      Measurement range
      100/1000/10000 A
      STANDARDS
      Certifications
      UL, CAN/CSA-C22.2 No. 61010-1, 3rd Edition, 2012-5, CE
      Electrical safety, Maximum height (m)
      2000
      Standards
      Recycling European Directive 2002/96/EC, EN 61326-1, UL 61010-1, 3rd Edition, 2012-05-11, IEC 61010-1, 3rd Edition
      CURRENT MEASUREMENT CIRCUIT
      Installation category
      CAT III 600 V
      Nominal current (In)
      Depending on the clamp
      Phase current measurement
      Transformadores con salida 0,250 A ó 0,333 V
      Phase current measuring range
      1…200 % In
      Maximum input current consumption
      0,0004 VA
      Maximum pulse current
      3 x In A
      Minimum current measurement
      Depending on the clamp
      VOLTAGE MEASUREMENT CIRCUIT
      Installation category
      CAT III 600 V
      Consumption
      0,15 VA
      Sampling frequency
      45…65 Hz
      Input impedance
      2,4 MΩ
      Voltage measuring range
      10…600 Vac
      Minimum measurement voltage (Vstart)
      10 V ac
      COMMUNICATIONS
      Band
      2,4 GHz.
      Networks
      UMTS/HSPA: 850/900/1900/2100 MHz. # GSM /GPRS /EDGE: 850/900/1800/1900 MHz.
      Maximum output power
      UTMS/3G (Potencia Clase 3): 24dBM, GSM850/900 (Potencia Clase 4): 33dBM, GSM1800/1900 (Potencia Clase 1): 30 dBM.
      Connection mechanism
      Wi-Fi
      ELECTRICAL SAFETY
      Insulation
      Double-insulated electric shock protection class II (IEC 61010-1)
      DIGITAL INPUTS
      Input/output insulation
      2,7 kV
      Quantity
      2
      Type
      Potential-free contact
      Maximum short-circuit current
      5 mA
      Maximum open circuit voltage
      4…9 Vdc
      MEMORY
      Format
      FAT 32
      Write time
      1s, 1m, 5m, 15m, 1h, 1d
      DIGITAL TRANSISTOR OUTPUTS
      Quantity
      2
      Type
      Opto MOSFET
      Maximum current
      90 mA
      Maximum voltage
      48 Vc.c.
      MECHANICAL CHARACTERISTICS
      Weight (kg)
      4
      INTERNAL BATTERY
      Capacity
      220 mAh
      Type
      Litio
      Useful life
      10 a?os
      Voltage
      3 Vc.c.
      MEASUREMENT ACCURACY
      Current asymmetry (Ka)
      Class A (IEC 61000-4-30)
      Voltage asymmetry (Ka)
      Class A (IEC 61000-4-30)
      Current unbalance (Kd)
      Class A (IEC 61000-4-30)
      Voltage unbalance (Kd)
      Class A (IEC 61000-4-30)
      Frequency measurement
      Class 0,1 (45…65 Hz)
      Phase current measurement
      class 0,2 (1…200 % In) (IEC 61557-12)
      Reactive energy measurement (kvarh)
      Class 1 (IEC 62053-23)
      Reactive power measurement (kvar)
      Class 1 ± 1 digit (IEC 61557-12) (Vn ac 230/110)
      Apparent power measurement (kVA)
      class 0,5 ± 1 digit (IEC 61557-12) (Vn ac 230/110)
      Active energy measurement (kWh)
      Class 0,5S (IEC 62053-22)
      Phase voltage measurement
      Class 0.2 0,2 (10…1000 VF-N c.a.) (IEC 61557-12)
      Pinst. Flicker
      3 % (IEC 61000-4-15)
      Pst Flicker
      5 % (0,2 … 10Pst) (IEC 61000-4-15)
      Current harmonics (THD)
      (up 50th) Class 1 (IEC 61000-4-7)
      Voltage harmonics (THD)
      (up 50th) Class 1 (IEC 61000-4-7)