05 标准规范
本开关及同时提供的辅助设备和特殊工具符合供货 时所涉及的法律、条例及标准。
一符合标准 IEC-60056.
电 压 高 于 1kV 的交流开关设备标准-VDE0670 第101-108 部分。
实际技术数据将以供货时的铬牌数据和所附技
术文件为准。
10 工作温度
本开关工作所适用的环流温度范围为
30°C-+55°C
The 3AP1 circuit-breaker is of the self-compression type and uses SF6-gas for insulation and arc-quench- ing purposes, It is of triple-pole outdoor design.
The breaker has for all three phases a common operat- ing mechanism and is therefore suitable for triple-polar auto-reclosing.
05 Standard specifications
The circuit-breaker, together with the equipment and special tools also supplied, is in conformity with the statutory laws, rules and standards applying at the time of delivery.
-The specifications in IEC-Publications 60056.
The regulations for AC switchgear for voltages over 1 kV-VDE 0670 Part 101 to Part 108.
The technical data actually applying to the switching device supplied are stated on the rating plate and in the appended documentation.
10 Operating temperatures
The circuit-breakers are designed for operation in an ambient temperature range from-30C to+55 ℃.
15 符 合IEC 标准的额定绝缘水平 15 Insulation rating as per IEC
额定电压 |
kV |
145 |
额定频率 |
Hz |
50:60 |
额定工频耐受电压(有效值) |
|
|
对地 |
kV |
275 |
断□间 |
kV |
275 |
相 间 |
kV |
275 |
额定雷电冲击电压 |
|
|
(1.2/50μs): |
|
|
对地 |
kV |
650 |
断□间 |
kV |
650 |
-相面 |
kV |
650 |
于弧距离 -对地 -断口间 相间 |
mm mm mm |
1250 1200
1360 |
最小爬电距离 -对地(25.6mm/kV) -区□间(25,6mm/kV) |
mm mm |
3718 3748 |
92700048174 C 1-1
3A-10080/002
空气的绝缘能力随着高度的升高而降低,安装高压超过 1000米时,外部绝缘的耐压强度为:
The insulating capacity of air decreases as the altitude increases. For installation at altitudes above 1000 m, the dielectric strength of air of the switching device is determined as follows
额定电压
在安装现场
(绝缘水平)
除数Kn的计算公式:
Rated voltage (Insulation
Rated voltage level)
at erectian site
(Insulation level) K
The divisor ka results from
H.. 安装高度m
m..系数
m=1 工频耐受电压,雷电冲击耐受电压以及相间
操作冲击耐受电压
m=0,9 断□间操作冲击耐压
m=0.75 相对地操作冲击耐压
根 据 IEC 69405/96
H... altitude in m
m..factor
m =1 for power frequency withstand voltage and light-
ning withstand voltage as well as switching impulse voltage between phases.
m =0.9 switching impulse withstend valtage across interrupt unit.
m =0,75 for switching impulse withstenyoitage to earth.
(From IEC 69405/96)
20 电 气 数 据
20 Electrical data
额定电压 |
kV |
145 |
|
Rated voltage |
kV |
145 |
|
|
额定须率 |
Hz |
50/60 |
|
Rated frequency |
Hz |
50760 |
|
|
额定电流 |
A |
3150 |
|
Rated current |
A |
3150 |
|
|
额定短路开断电流 |
kA |
40 |
|
Rated short-circuit breaking current |
kA |
40 |
|
|
出线端短路时的 瞬态恢复电压 |
|
根据VDE.IEC标准 |
|
Transient recovery voltage |
|
acg |
|
IEC |
under terminaf fault conditions |
|
|||||||
额定关合电流 |
kA |
100 |
|
Rated making current |
kA |
100 |
|
|
额定短路持续时间 |
S |
3 |
|
Rated short-circuit duration |
S |
3 |
|
|
操作顺序 |
|
0-0.3s-CO-3 min-CO 或CO-15s-CO |
|
|
|
min -C? ED:d5S |
CO |